System messages
12.3 Faults and alarms
Cause:
The macro cannot be executed.
Fault value (r0949, interpret hexadecimal):
ccccbbaa hex:
cccc = preliminary parameter number, bb = supplementary information, aa = fault cause
Fault causes for the trigger parameter itself:
19: Called file is not valid for the trigger parameter.
20: Called file is not valid for parameter 15.
21: Called file is not valid for parameter 700.
22: Called file is not valid for parameter 1000.
23: Called file is not valid for parameter 1500.
24: Data type of a TAG is incorrect (e.g. Index, number or bit is not U16).
Fault causes for the parameters to be set:
25: Error level has an undefined value.
26: Mode has an undefined value.
27: A value was entered as string in the tag value that is not "DEFAULT".
31: Entered drive object type unknown.
32: A device was not able to be found for the determined drive object number.
34: A trigger parameter was recursively called.
35: It is not permissible to write to the parameter via macro.
36: Check, writing to a parameter unsuccessful, parameter can only be read, not available, incorrect data type, value range
or assignment incorrect.
37: Source parameter for a signal interconnection was not able to be determined.
38: An index was set for a non-indexed (or CDS-dependent) parameter.
39: No index was set for an indexed parameter.
41: A bit operation is only permissible for parameters with the parameter format DISPLAY_BIN.
42: A value not equal to 0 or 1 was set for a bit operation.
43: Reading the parameter to be changed by the bit operation was unsuccessful.
51: Factory setting for DEVICE may only be executed on the DEVICE.
61: The setting of a value was unsuccessful.
Remedy:
- Check the parameter involved.
- Check the macro file and signal interconnection.
F07083
Template: ACX file not found
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Message value:
Parameter: %1
Component:
None
Response:
NONE
Acknowledgment: IMMEDIATELY
Cause:
The template to be executed was not able to be found.
Fault value (r0949, interpret decimal):
Parameter number with which the execution was started.
Remedy:
- Check whether the corresponding template number is available.
F07084
Macro: Condition for WaitUntil not fulfilled
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Message value:
Parameter: %1
Component:
None
Response:
NONE
Acknowledgment: IMMEDIATELY
504
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB