Acknowledgment: NONE
Cause:
A consistency error was detected when activating the configuration for the PROFINET interface (X150).
Alarm value (r2124, interpret decimal):
0: General consistency error
1: Error in the IP configuration (IP address, subnet mask or standard gateway).
2: Error in the station names.
3: DHCP was not able to be activated, as a cyclic PROFINET connection already exists.
5: Standard gateway is also set at the Industrial Ethernet interface (X127).
6: Standard station name is also set at the Industrial Ethernet interface (X127).
7: IP address is located in the same subnet as the IP address of the Industrial Ethernet interface (X127).
Note:
For alarm value = 0, 1, 2, 3, 4, 5, 7, the following applies: the configuration was not changed.
For alarm value = 6 the following applies: The new configuration was however activated.
DHCP: Dynamic Host Configuration Protocol
Remedy:
Reinitialize the station using the "Edit Ethernet node" screen form (e.g. with Startdrive commissioning tool).
A08566
IIOT: Syntax error in configuration file
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Message value:
-
Component:
None
Response:
NONE
Acknowledgment: NONE
Cause:
A syntax error has been detected in the configuration file for the IIoT interface (X128). The saved configuration file has not
been loaded.
Note:
IIoT: Industrial Internet of Things
Remedy:
Reinitialize the station using the "Edit Ethernet node" screen form (e.g. with Startdrive commissioning tool).
A08567
IIoT: Consistency error for adjustable parameters
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Message value:
%1
Component:
None
Response:
NONE
Acknowledgment: NONE
Cause:
A consistency error was detected when activating the configuration for the IIoT interface (X128).
Alarm value (r2124, interpret decimal):
0: General consistency error
1: Error in the IP configuration (IP address, subnet mask or standard gateway).
2: Error in the station names.
5: Standard gateway is also set at the PROFINET interface.
6: The station name is also set at the PROFINET interface.
7: The IP address is located in the same subnet as the IP address of the PROFINET interface.
Note:
For alarm value = 0, 1, 2, 5, 7 the following applies: the configuration was not changed.
For alarm value = 6 the following applies: The new configuration was however activated.
IE: Industrial Ethernet
Remedy:
Reinitialize the station using the "Edit Ethernet node" screen form (e.g. with Startdrive commissioning tool).
A08800
PROFIenergy energy-saving mode active
Message class:
Communication error to the higher-level control system (9)
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB
System messages
12.3 Faults and alarms
537