Acknowledgment: IMMEDIATELY
Cause:
An upgrade (project/firmware download) was initiated on the memory card.
While this fault is active, the corresponding update takes place with plausibility and consistency checks. After this,
depending on the command option, a new boot (reset) for the converter is initiated.
Caution:
While upgrading and while this fault is active, it is not permissible to switch off the converter.
If the operation is interrupted, this can destroy the file system on the memory card. The memory card will then no longer
work properly and must be repaired.
Remedy:
Not necessary.
The fault is automatically withdrawn after the upgrade has been completed.
F01072
Memory card restored from the backup copy
Message class:
General drive fault (19)
Message value:
-
Component:
Control Unit (CU)
Response:
NONE
Acknowledgment: IMMEDIATELY
Cause:
The converter was switched-off while writing to the memory card. This is why the visible partition became defective.
After switching on, the data from the non-visible partition (backup copy) were written to the visible partition.
Remedy:
Check that the firmware and parameterization is up-to-date.
A01073
POWER ON required for backup copy on memory card
Message class:
General drive fault (19)
Message value:
-
Component:
Control Unit (CU)
Response:
NONE
Acknowledgment: NONE
Cause:
The parameter assignment on the visible partition of the memory card has changed.
In order that the backup copy on the memory card is updated on the non-visible partition, it is necessary to carry out a
POWER ON or hardware reset (p0972) of the Control Unit.
Note:
It is possible that a new POWER ON is requested via this alarm (e.g. after saving with p0971 = 1).
Remedy:
- Carry out a POWER ON (switch-off/switch-on) for the Control Unit.
- Carry out a hardware reset (RESET button, p0972).
F01082
Parameter error when running up from data backup
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Message value:
Parameter: %1, index: %2, fault cause: %3
Component:
None
Response:
OFF2
Acknowledgment: IMMEDIATELY
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB
System messages
12.3 Faults and alarms
449