Cause:
The WaitUntil condition set in the macro was not fulfilled in a certain number of attempts.
Fault value (r0949, interpret decimal):
Parameter number for which the condition was set.
Remedy:
Check and correct the conditions for the WaitUntil loop.
F07085
Drive: Open-loop/closed-loop control parameters changed
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Message value:
Parameter: %1
Component:
None
Response:
NONE
Acknowledgment: IMMEDIATELY
Cause:
Open-loop/closed-loop control parameters have had to be changed.
Possible causes:
1. As a result of other parameters, they have exceeded the dynamic limits.
2. They cannot be used due to the fact that the hardware detected not having certain features.
3. The value is estimated as the thermal time constant is missing.
4. Motor temperature model 1 is activated as thermal motor protection is missing.
See also: p1082 (Maximum speed)
Remedy:
Not necessary.
It is not necessary to change the parameters as they have already been correctly limited.
F07086
Units changeover: Parameter limit violation due to reference value change
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Message value:
Parameter: %1
Component:
None
Response:
NONE
Acknowledgment: IMMEDIATELY
Cause:
A reference parameter was changed in the system. This resulted in the fact that for the parameters involved, the selected
value was not able to be written in the per unit notation.
The values of the parameters were set to the corresponding violated minimum limit/maximum limit or to the factory setting.
Possible causes:
- The steady-state minimum limit/maximum limit or that defined in the application was violated.
Fault value (r0949, parameter):
Diagnostics parameter to display the parameters that were not able to be re-calculated.
See also: p0304, p0305, p2000, p2002, p2003
Remedy:
Check the adapted parameter value and if required correct.
F07088
Units changeover: Parameter limit violation due to units changeover
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Message value:
Parameter: %1
Component:
None
Response:
NONE
Acknowledgment: IMMEDIATELY
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB
System messages
12.3 Faults and alarms
505