System messages
12.3 Faults and alarms
F01325
Topology: Component number not included in target topology
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Message value:
Component number: %1
Component:
None
Response:
NONE
Acknowledgment: IMMEDIATELY
Cause:
The component referenced in a data set (e.g. PDS, MDS or EDS) is not contained in the target topology.
Fault value (r0949, interpret decimal)
Remedy:
Establish consistency between the topology and data set configuration.
A01330
Topology: Quick commissioning not possible
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Message value:
Fault cause: %1, supplementary information: %2, preliminary component number: %3
Component:
None
Response:
NONE
Acknowledgment: NONE
Cause:
Unable to carry out a quick commissioning. The existing actual topology does not fulfill the requirements.
Remedy:
- Check the motor connection.
- Carry out a POWER ON (switch-off/switch-on).
F01356
Topology: There is a defective component
Message class:
Hardware/software error (1)
Message value:
Fault cause: %1, Component number: %2, Connection number: %3
Component:
None
Response:
NONE
Acknowledgment: IMMEDIATELY
Cause:
The actual topology indicates at least one defective component.
Note:
Pulse enable is withdrawn and prevented.
Remedy:
Replace the defective component and restart the system.
F01380
Topology: Actual topology EEPROM defective
Message class:
Hardware/software error (1)
Message value:
Preliminary component number: %1
Component:
None
Response:
NONE
Acknowledgment: POWER ON
Cause:
When detecting the actual topology, a component with a defective EEPROM was detected.
Fault value (r0949, interpret hexadecimal):
bbbbaaaa hex:
bbbb = reserved
aaaa = preliminary component number of the defective components
Remedy:
Output the fault value and remove the defected component.
A01382
Topology: Sensor Module incorrectly inserted
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Message value:
Component: %1, to %2, %3, connection: %4
Component:
None
Response:
NONE
458
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB