12.3 Faults and alarms
Remedy:
For parallel connections, only Active Interface Modules (AIM) with identical EEPROM versions may be used.
F05069
Parallel connection: AIM firmware versions different
Message class:
General drive fault (19)
Message value:
Parameter: %1
Component:
-
Response:
NONE
Acknowledgment: IMMEDIATELY
Cause:
The firmware versions of the Active Interface Module (AIM) do not match.
Fault value (r0949, interpret decimal):
Parameter in which the first different version number was detected.
Remedy:
For parallel connections, only Active Interface Modules (AIM) with identical firmware versions may be used.
F06310
Supply voltage (p0210) incorrectly parameterized
Message class:
Network fault (2)
Message value:
-
Component:
None
Response:
NONE
Acknowledgment: IMMEDIATELY
Cause:
For AC/AC drive units, the measured DC link voltage lies outside the tolerance range after precharging has been completed.
The following applies for the tolerance range: 1.16 * p0210 < r0070 < 1.6 * p0210
Note:
The fault can only be acknowledged when the drive is switched off.
See also: p0210 (Device supply voltage)
Remedy:
- Check the parameterized supply voltage and if required change (p0210).
- Check the line voltage.
See also: p0210 (Device supply voltage)
F07011
Drive: Motor overtemperature
Message class:
Motor overload (8)
Message value:
%1
Component:
Motor
Response:
OFF2
Acknowledgment: IMMEDIATELY
Cause:
The calculated motor temperature is too high.
Possible causes:
- Motor overloaded.
- Motor ambient temperature too high.
- Sensor wire breakage.
Fault value (r0949, interpret decimal):
200:
Motor temperature model 1 (I2t): temperature too high.
300:
Motor temperature model 3: after the monitoring time has expired, the temperature is still higher than the alarm threshold.
301:
Motor temperature model 3: temperature is too high, or the model has not been parameterized.
302:
Motor temperature model 3: Encoder temperature is not within the valid range.
400:
Additional motor overload protection: the load is too high.
502
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB