Appendix
A.3 Parameters
Note
The buffer parameters are cyclically updated (states are indicated in r2139).
Fault buffer structure (general principle):
r0945[0], r0949[0] or r2133[0], r2130[0], r0948[0], r2136[0], r2109[0] --> fault 1 (oldest active fault) of the active
incident
. . .
r0945[7], r0949[7] or r2133[7], r2130[7], r0948[7], r2136[7], r2109[7] --> fault 8 (latest active fault) of the active
incident
For more than 8 active faults, only the entries are overwritten at the eighth position (index 7).
History of acknowledged faults:
If a fault incident is acknowledged, then all alarms of the 1st fault incident are transferred into the 2nd fault incident,
this becomes the 1st acknowledged fault incident.
The 2nd incident is transferred into the 3rd, the 3rd into the 4th etc. The last incident is rejected.
r0945[8], r0949[8] or r2133[8], r2130[0], r0948[8], r2136[8], r2109[8] --> fault 1 of the 1st acknowledged incident
. . .
r0945[16], r0949[16] or r2133[16], r2130[16], r0948[16], r2136[16], r2109[16] --> fault 1 of the 2nd acknowledged
incident
. . .
r0945[56], r0949[56] or r2133[56], r2130[56], r0948[56], r2136[56], r2109[56] --> fault 1 of the 7th acknowledged
incident
. . .
r0945[63], r0949[63] or r2133[63], r2130[63], r0948[63], r2136[63], r2109[63] --> fault 8 (oldest fault that has gone)
of the 7th acknowledged incident
r0948[0...63]
Fault time received in milliseconds
 
Data type: Unsigned32
Read permission:
Write permission:
Parameter group:
Unit: ms
Description:
Displays the system runtime in milliseconds when the fault occurred.
Dependency:
See also: r0945, r0947, r0949, r2109, r2114, r2130, r2133, r2136, r3122
NOTICE
The time comprises r2130 (days) and r0948 (milliseconds).
Note
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
The structure of the fault buffer and the assignment of the indices is shown in r0945.
When the parameter is read via PROFIdrive, the TimeDifference data type applies.
r0949[0...63]
Fault value
 
Data type: Integer32
Read permission:
Write permission:
Parameter group:
Unit: -
Description:
Displays additional information about the fault that occurred (as integer number).
Dependency:
See also: r0945, r0947, r0948, r2109, r2130, r2133, r2136, r3122
Note
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
The structure of the fault buffer and the assignment of the indices is shown in r0945.
728
Visible in: Extended display
Read drive data or acknowledge messages
Edit device configuration or drive applications
Faults / alarms
Visible in: Extended display
Read drive data or acknowledge messages
Edit device configuration or drive applications
Faults / alarms
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB
 
 