System messages
12.3 Faults and alarms
Cause:
A data save in the non-volatile memory was not able to be successfully carried out.
- Non-volatile memory is defective.
- Insufficient space in the non-volatile memory.
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
- Try to save again.
- Replace the memory card or Control Unit.
F01110
CU: More than one SINAMICS G on one Control Unit
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Message value:
%1
Component:
None
Response:
NONE
Acknowledgment: IMMEDIATELY
Cause:
More than one SINAMICS G type power unit is being operated from the Control Unit.
Fault value (r0949, interpret decimal):
Number of the second drive with a SINAMICS G type power unit.
Remedy:
Only one SINAMICS G drive type is permitted.
F01111
CU: Mixed operation of drive units illegal
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Message value:
%1
Component:
None
Response:
NONE
Acknowledgment: IMMEDIATELY
Cause:
Illegal operation of various drive units on one Control Unit:
- SINAMICS S together with SINAMICS G
- SINAMICS S together with SINAMICS S Value or Combi
Fault value (r0949, interpret decimal):
Number of the first drive object with a different power unit type.
Remedy:
Only power units of one particular drive type may be operated with one Control Unit.
F01122
Frequency at the measuring probe input too high
Message class:
Application/technological function faulted (17)
Message value:
%1
Component:
None
Response:
OFF1
Acknowledgment: IMMEDIATELY
Cause:
The frequency of the pulses at the measuring probe input is too high.
Fault value (r0949, interpret decimal):
1: DI/DO 9 (X122.8)
2: DI/DO 10 (X122.10)
4: DI/DO 11 (X122.11)
8: DI/DO 13 (X132.8)
16: DI/DO 14 (X132.10)
32: DI/DO 15 (X132.11)
64: DI/DO 8 (X122.7)
128: DI/DO 12 (X132.7)
Remedy:
Reduce the frequency of the pulses at the measuring probe input.
452
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB