Remedy:
- Correct the target position.
- Change the negative software limit switch (c2578, p2580).
See also: c2578 (EPOS negative software limit switch), p2580 (EPOS negative software limit switch), c2582 (EPOS software
limit switch activation)
A07480
EPOS: Positive software limit switch reached
Message class:
Application/technological function faulted (17)
Message value:
-
Component:
None
Response:
NONE
Acknowledgment: NONE
Cause:
The axis is at the position of the positive software limit switch. An active traversing block was interrupted.
Remedy:
- Correct the target position.
- Change the positive software limit switch (c2579, p2581).
See also: c2579 (EPOS positive software limit switch), p2581 (EPOS positive software limit switch), c2582 (EPOS software
limit switch activation)
F07481
EPOS: Axis position < negative software limit switch
Message class:
Application/technological function faulted (17)
Message value:
-
Component:
None
Response:
OFF1
Acknowledgment: IMMEDIATELY
Cause:
The actual position of the axis is less than the position of the negative software limit switch.
Remedy:
- Correct the target position.
- Change the negative software limit switch (c2578, p2580).
See also: c2578 (EPOS negative software limit switch), p2580 (EPOS negative software limit switch), c2582 (EPOS software
limit switch activation)
F07482
EPOS: Axis position > positive software limit switch
Message class:
Application/technological function faulted (17)
Message value:
-
Component:
None
Response:
OFF1
Acknowledgment: IMMEDIATELY
Cause:
The actual position of the axis is greater than the position of the positive software limit switch.
Remedy:
- Correct the target position.
- Change the positive software limit switch (c2579, p2581).
See also: c2579 (EPOS positive software limit switch), p2581 (EPOS positive software limit switch), c2582 (EPOS software
limit switch activation)
A07483
EPOS: Travel to fixed stop clamping torque not reached
Message class:
Application/technological function faulted (17)
Message value:
-
Component:
None
Response:
NONE
Acknowledgment: NONE
Cause:
The fixed stop in the traversing block was reached without the clamping torque/clamping force having been achieved.
Remedy:
- Check the torque limits (p1520, p1521).
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2