Diagnostics

7.2 Message classes in accordance with PROFIdrive

7.2
Message classes in accordance with PROFIdrive
Message
class
168
PN
Explanation of the message class according to PROFIdrive -
1)
(hex)
cause and remedy.
1
9000
Hardware fault/software error
A hardware or software malfunction has been identified.
● Carry out a POWER ON for the relevant component.
● If it occurs again, replace again.
2
9001
Line fault
A line supply fault has occurred (phase failure, voltage level, etc.).
● Check the line supply/fuses
● Check the supply voltage.
● Check the wiring.
3
9002
Supply voltage fault
An electronics power supply fault (24 V) has been identified. Check the wiring.
● Check the voltage level.
4
9003
DC link overvoltage
The DC-link voltage has assumed an inadmissibly high value.
● Check the dimensioning of the system (line supply, reactor, voltages).
● Check the infeed settings.
5
9004
Power electronics fault
An inadmissible operating state of the power electronics has been identified
(overcurrent, overtemperature, IGBT failure,...).
● Check compliance with the permissible load cycles.
● Check the ambient temperatures (fan).
6
9005
Electronic component overload
The temperature in the component has exceeded the highest permissible limit.
● Check the ambient temperature / control cabinet ventilation.
7
9006
Ground fault / inter-phase short-circuit detected
A ground fault / inter-phase short-circuit has been identified in the power ca‐
bles or in the motor windings.
● Check the power cables (connection).
● Check the motor.
8
9007
Motor overload
The motor was operated outside the permissible limits (temperature, current,
torque...).
● Check the load cycles and set limits.
● Check the ambient temperature / motor cooling.
9
9008
Communication error to the higher-level controller
The communication to the higher-level controller is faulted or interrupted.
Check the state of the higher-level controller.
● Check the communication connection/wiring.
● Check the bus configuration / clock cycles.
SINAMICS S210 servo drive system