5-184 Emergency power conservation recovery procedures
Emergency power conservation
Emergency shutdown of one unit of MSB7s
23
24
At the shelf that contains the inactive MSB7
25
26
27
28
29
30
297-8021-545 Standard 14.02 May 2001
where
plane_no
is the ENET plane number
To busy the first link recorded in step 18 from the ENET card to the PM unit,
type
>BSY
plane_no
and press the Enter key.
where
plane_no
is the ENET plane number, recorded in step 19link_nois the network
link number, recorded in step 19
Repeat steps 21 to 23 for each speech link recorded in step 18. Continue the
procedure.
WARNING
Static electricity damage
Wear a wrist strap that connects to a wrist-strap grounding
point on the frame supervisory panel (FSP) or the modular
supervisory panel (MSP) to handle circuit cards. The wrist
strap protects the cards against static electricity damage.
Unseat the NT6X69 message protocol card from slot 20.
Unseat the NT6X45 signaling processor card from slot 16.
Unseat the NT6X45 master processor card from slot 11.
Unseat the NT6X46 signaling-processor memory card from slot 15.
WARNING
Loss of service
If you power down the active unit of the MSB7 or the power
converter in slot 1, service loss occurs.
Pull down and set the handle of the NT2X70 power converter in slot 25
POWER switch to the OFF position.
Repeat steps 2 to 29 for one unit of each MSB7.
(continued)
LINK
link_no