5-48 Emergency power conservation recovery procedures
Emergency power conservation
Restoring the LPP LIM to duplex operation
4
5
6
At the MAP
7
8
9
297-8021-545 Standard 14.02 May 2001
lim_no
is the number of the LIM that you post (0 to 16)
Example of a MAP response:
LIM
1
ISTB
Links_OOS Taps_OOS
Unit0: ManB
Unit1: InSv
To load the LIM unit that you powered up in step 1, type
>LOADPM UNIT unit_no
and press the Enter key.
where
unit_no
is the number of the LIM unit (0 or 1)
To return the LIM unit that you powered up in step 1 to service, type
>RTS
UNIT
unit_no
and press the Enter key.
where
unit_no
is the number of the LIM unit (0 or 1)
To access the F-bus level of the MAP display, type
>FBUS
and press the Enter key.
To return the F-bus to service, type
>RTS
FBUS
fbus_no
and press the Enter key.
where
fbus_no
is the number of F-bus (0 or 1)
Note: F-bus 0 associates with LIM unit 0 and F-bus 1 associates with LIM
unit 1.
Repeat steps 1 to 7 for each LPP that you converted to simplex operation to
conserve emergency power.
Return to the procedure Emergency power conservation—Restoration in this
document. Proceed when the step-action procedure directs you to go.
(end)