5-168 Emergency power conservation recovery procedures
Emergency power conservation
Emergency shutdown of one SuperNode SE CM plane
22
23
At the CM/SLM shelf
24
25
297-8021-545 Standard 14.02 May 2001
To access the MC level of the MAP display, type
>MC
and press the Enter key.
Example of a MAP response:
CM 0
MC 0 MC 1
.
.
To manually busy the MC that corresponds to the inactive CPU, type
>BSY
mc_number
and press the Enter key.
where
mc_number
is the number of the inactive CPU (0 or 1)
Example of a MAP response:
Maintenance action submitted.
MC busied OK.
WARNING
Static electricity damage
Wear a wrist strap that connects to the wrist-strap grounding
point of a frame supervisory panel (FSP) to handle circuit
cards. The wrist strap protects the cards against static
electricity damage.
Press down and release the power switch to power down the inactive CPU
plane. The power switch is on the faceplate of the NTDX15 power converter.
Note: The power converter appears in slots 4F through 6F for plane 0.
The power converter is in slots 33F through 35F for plane 1.
The procedure is complete.
(end)