2-104 System level recovery procedures
Recovering from a dead system in a SuperNode SE switch
96
97
At the IOC
98
99
100
101
102
103
104
105
297-8021-545 Standard 14.02 May 2001
Determine if you must recover additional IOCs and MAPs.
If you
must recover additional IOCs
and MAPs
do not need to recover additional
IOCs and MAPs
Restore power to all power inverters that remain in the office.
Locate the IOC to recover.
If the controller
is IOC
is IOM
Turn ON the power converters on the IOC.
Note: The vintage of IOC determines if the IOC has one or two power
converters.
While you press the RESET button on one of the IOC power converters, lift
the associated circuit breaker switch on the FSP.
Release the RESET button.
Repeat steps 98 through 101 for each IOC to recover. Continue this
procedure at step 103.
To access the IOD level of the MAP display, type
>IOD
and press the Enter key.
To access the IOC level of the MAP display, type
>IOC
ioc_no
and press the Enter key.
where
ioc_no
is the number of the IOC or input/output module (IOM) to recover
To manually busy the IOC or IOM, type
>BSY
ioc_no
and press the Enter key.
where
ioc_no
is the number of the IOC or IOM
Do
step 97
step 109
Do
step 99
step 103
(continued)