3-4 Node level recovery procedures
Recovering the enhanced network
Recovering the enhanced network
At your current location
1
2
3
297-8021-545 Standard 14.02 May 2001
WARNING
Contact ETAS or your next level of support
If an equipment outage that affects service occurs, contact
Emergency Technical Assistance Service (ETAS) of Nortel
before you perform the procedure. You can also contact
the next level of support.
CAUTION
Loss of service
Manual interruption during automatic system recovery
actions can interrupt or delay automatic recovery. The
interruption can prolong service outage.
CAUTION
Potential service interruption
Do not perform this procedure while a restart is in
progress. When you log on after a restart, wait 5 min to
allow the ENET time to try to recover.
Determine if the local operating company keeps a log book of office image
files.
If a log book
is kept
is not kept
From the local office log book, record the latest image file name. Go to step 7.
To access table ENINV, type
>TABLE
ENINV
and press the Enter key.
(continued)
Do
step 2