5-26 Emergency power conservation recovery procedures
Emergency power conservation
Restoring the junctored network to duplex operation
4
5
6
7
At the MAP display
8
297-8021-545 Standard 14.02 May 2001
a
Pull up and set the handle of the POWER switch to the RESET position
and hold.
b
Set the handle of the converter circuit breaker on the FSP or MSP up until
it clicks into place.
c
Release the handle.
Go to step 8.
Power up the converter as follows:
a
Pull up and set the handle of the POWER switch to the RESET position
and hold until the CONVERTER FAIL LED turns off.
b
Release the handle.
Go to step 8.
Determine if the FSP or MSP has circuit breakers.
If the FSP or MSP
has circuit breakers
does not have circuit breakers
Power up the converter as follows:
a
Pull up and set the handle of the POWER switch to the ON position.
b
Press and hold the RESET button on the power converter.
c
Set the handle of the converter circuit breaker on the FSP or MSP up until
it clicks into place.
d
Release the RESET button.
Go to step 8.
Power up the converter as follows:
a
Pull up and set the handle of the POWER switch to the ON position.
b
Press the RESET button on the power converter until the CONVERTER
FAIL LED turns off.
c
Release the RESET button.
To access the NET level of the MAP display, type
>MAPCI;MTC;NET
and press the Enter key.
Example of a MAP response:
(continued)
Do
step 6
step 7