Nortel DMS-100 Manual page 454

Hide thumbs Also See for DMS-100:
Table of Contents

Advertisement

Emergency shutdown of one DMS SuperNode CM plane
4
5
6
At the CM reset terminal for the inactive CPU
7
8
Emergency power conservation recovery procedures
If
both CPU 0 and CPU 1 have faults
Do not continue this procedure until you clear the faults on a minimum of one
of the CPUs. To clear the faults you must clear the correct CM alarms. Go
to step 2 when a minimum of one of the CPUs is fault free.
To switch activity, type
>SWACT
and press the Enter key.
Example of a MAP display
Switch of activity will cause the CM to be running on
the inactive CPU's processor clock. System will drop
SYNC and then re–SYNC in order to switch to the active
CPU's clock.
Do you wish to continue?
Please confirm ("YES", "Y", "NO", or "N"):
To confirm the command, type
>YES
and press the Enter key.
WARNING
Loss of service
Make sure that you do not jam the active CPU. A cold restart
occurs if you jam the active CPU while the CM is out of
sync. The word Active on the top banner of the display
identifies the reset terminal for the active CPU.
To jam the inactive CPU, type
>\JAM
and press the Enter key.
RTIF response
Please confirm: (YES/NO)
To confirm the command, type
>YES
and press the Enter key.
DMS-100 Family NA100 Recovery Procedures LET0015 and up
Emergency power conservation
5-103
(continued)