Restoring the MSB7 to duplex operation
7
Reseat the NT6X45 signaling processor card in slot 16.
8
Reseat the NT6X69 message protocol card in slot 20.
At the MAP terminal
9
To access the peripheral module (PM) level of the MAP display, type
>MAPCI;MTC;PM
and press the Enter key.
10
To post the MSB7, type
>POST
MSB7
and press the Enter key.
where
pm_no
is the PM identification number (0 to 999)
Example of a MAP response:
MSB7
0 ISTb
, PSide
0
Unit0:
Unit1:
11
To identify the network type and network links that associate with the manual
busy MSB7 unit, type
>TRNSL C
and press the Enter key.
Example of a MAP response for JNET:
LINK 0: NET 0 3 12;CAP MS;Status:OK
LINK 1: NET 1 3 12;CAP MS;Status:MBsy
LINK 2: NET 0 3 28;CAP MS;Status:OK
LINK 3: NET 1 3 28;CAP MS;Status:MBsy
LINK 4: NET 0 3 44;CAP MS;Status:OK
...
LINK 31 NET 1 3 63;CAP MS;Status:MBsy
Note: Links 5 to 30 do not appear.
Example of a MAP response for ENET:
DMS-100 Family NA100 Recovery Procedures LET0015 and up
Emergency power conservation recovery procedures
Emergency power conservation
pm_no
Links_OOS: CSide
ManB
Mtce
Insv
(continued)
0
5-61