5-6 Emergency power conservation recovery procedures
Emergency power conservation
Restoration
(end)
9
10
11
12
13
14
15
16
297-8021-545 Standard 14.02 May 2001
To recover a minimum of one junctored network (JNET) shelf, perform the
procedure Restoring the junctored network to duplex operation in this
document. If you power down a minimum of one JNET shelf to conserve
emergency backup power, perform the procedure.
To recover a minimum of one enhanced network ENET shelf, perform the
procedure Restoring the enhanced network to duplex operation in this
document. If you power down a minimum of one ENET shelf to conserve
emergency backup power, perform the procedure .
To recover a minimum of one of the following, perform the procedure
Restoring LGCs, LTCs and DTCs to duplex operation in this document:
the line group controller (LGC) unit
the line trunk controllers (LTC) unit
the digital trunk controller (DTC) unit
If you power down the LGCs, LTCs or DTCs to conserve emergency power,
perform this procedure.
To recover the line concentrating module (LCM) units, perform the procedure
Restoring LCMs to duplex operation in this document. If you power down a
minimum of one LCMs to conserve emergency power, perform this
procedure.
To recover the line module (LM) controllers, perform the procedure Restoring
line modules to duplex operation in this document. If you power down the LM
controllers to conserve emergency power, perform this procedure.
To recover a maintenance trunk module (MTM), perform the procedure
Returning maintenance trunk modules to service in this document. If you
power down one or more MTMs to conserve emergency power, perform the
procedure.
To clear all the alarms that remain on the MAP display, use the correct alarm
clearing NTPs.
The procedure is complete.