2-68 System level recovery procedures
Recovering from a dead system in a SuperNode switch
75
76
77
At the JNET shelf
78
297-8021-545 Standard 14.02 May 2001
SRSTATUS
OVERALL STATUS Pend:
0
Quit
VIEW: SYSTEM
2
View_
Pend InPrg
3
List_ MS
0
4
NET
0
5
SER1
0
6
SER2
1
7
SER3
11
8
9
SRSTATUS:
From the MAP display, determine the recovery status of the network.
Note: Network recovery status appears to the right side of the word NET
in the MAP display. The recovery status can be pending, in progress,
complete, or failed.
If the status of any network element
is failed
is pending
is other than listed here
Wait until there are no network elements pending recovery.
Go to step 75.
To recover the ENET manually, perform the procedure Recovering Enhanced
Network in this document.
When you complete the procedure, return to this point.
Go to step 74.
WARNING
Static electricity damage
Wear a wrist strap that connects to the wrist-strap grounding
point of a frame supervisory panel (FSP) or a modular
supervisory panel (MSP) to handle circuit cards. The wrist
strap protects the cards against static electricity damage.
Locate the first junctored network shelf to recover.
18%
InProg: 9%
Comp
Fail
0
2
0
IOD
0
6
0
Other 21
1
6
0
1
60
1
8
30
1
(continued)
Comp: 70%
Fail: 3%
11:52:34
Pend
InPrg
Comp
Fail
5
5
30
3
13
Do
step 77
step 76
step 90
2
3