Emergency shutdown of one remote oscillator shelf plane

Application
Use this procedure to conserve emergency backup power. To conserve
emergency backup power, shut down one plane of a remote oscillator shelf
(ROS). Remove power from the associated message switch plane before you
perform this procedure. Follow the procedure Emergency power
conservation—Emergency shutdown of one DMS SuperNode MS plane in this
document.
Action
The following flowchart is a summary of the procedure. Use the instructions
in the step-action procedure that follow the flowchart to perform the recovery
task.
Emergency power conservation recovery procedures 5-155
Emergency power conservation
DMS-100 Family NA100 Recovery Procedures LET0015 and up