Restoring the MSB7 to duplex operation
plane_no
is the network plane (0 or 1)
link_no
is the network link number
18
Repeat steps 16 and 17 until all the links between the manual busy MSB7 unit
and the network return to service. Go to step 26.
19
Determine the speech link numbers associated with the manual busy MSB7
unit. Even numbered speech links associate with unit 0. Odd numbered
speech links associate with unit 1.
Note: Speech links 0, 2, 4 and 6 associate with MSB7 unit 0 in the ENET
example response in step 11. Speech links 1, 3, 5, and 7 associate with
MSB7 unit 1. The speech links associated with MSB7 unit 1 are manual
busy.
20
Record the ENET plane number, shelf number, card number, and network link
number associated with the speech link. Perform this procedure for each
speech link recorded in step 19.
Note: An ENET example response appears in step 11. In this example,
speech link 3 associates with ENET plane 1, shelf 0, card 23, and network
link number 01.
21
To access the NET level of the MAP display, type
>NET
and press the Enter key.
22
To access the MAP display for the ENET card that associates with the first
link that you return to service, type
>SHELF
shelf_no;
and press the Enter key.
where
shelf_no
is the ENET shelf number recorded in step 20
card_no
is the ENET card number recorded in step 20
23
To return the first link recorded in step 19 to service, type
>RTS
plane_no
and press the Enter key.
where
plane_no
is the ENET plane number recorded in step 20
link_no
is the network link number recorded in step 20
24
To remove the deload status from the ENET card, type
>DELOAD
plane_no
and press the Enter key.
DMS-100 Family NA100 Recovery Procedures LET0015 and up
Emergency power conservation recovery procedures
Emergency power conservation
CARD
card_no
LINK
link_no
CLEAR
5-63
(continued)