Nortel DMS-100 Manual page 318

Hide thumbs Also See for DMS-100:
Table of Contents

Advertisement

Recovering enhanced link peripheral processors
If
HLIUs are SysB
HSLRs are SysB
any other type of Series III PM
types are SysB
Series III PMs are not SysB
20
Refer to procedure Recovering link peripheral processors in this document.
21
Select a system busy LIM to work on.
22
To post the system busy LIM, type
>POST
LIM
and press the Enter key.
where
lim_no
is the number of the LIM (0 to 16)
Example of a MAP response:
LIM
0
Unit0: SysB
Unit1: SysB
23
Determine if the LIM unit is system busy, resource unavailable (SysB RU).
Note: When a LIM unit is system busy, the message SysB (RU) appears
in the MAP response. This message appears to the right side of the LIM
unit number.
If
either LIM unit is SysB (RU)
neither LIM unit is SysB (RU) step 31
To clear the fault, refer to the Clearing a PM LIM critical alarm procedure in
24
Alarm and Performance Monitoring Procedures .
When you have completed the procedure, return to this point.
25
To access the LIS level of the MAP display, type
>LIS_no
and press the Enter key.
where
lis_no
is the number of the LIS (1, 2, or 3)
Recovery procedures for individual devices and services
lim_no
SysB
OOS
Links
LIS1
6
8
6
8
DMS-100 Family NA100 Recovery Procedures LET0015 and up
Do
step 1
step 7
step 20
step 32
OOS_Taps
LIS2
LIS3
8
8
8
8
Do
step 24
4-111
(continued)