5.1.9 Timing sequence

5.1.9.1 Timing sequence for power-on and servo turning on
Main power
Microprocessor
state
Servo readiness
(RDY)
Servo enabling
(SON)
Fan signal
PWM output
Electromagnetic
brake release
signal output
(BRK)
Position/speed/tor
que command
input
Note 1: The delay time from microprocessor initialization completion to servo readiness output can be set
through P4.54.
Note 2: The condition for the RDY output signal electric level to become low is: The servo has no fault and
main circuit DC voltage has been established, with voltage higher than 250V/430V (for 220V/400V series). If
the main circuit DC voltage is less than 170V/310V (for 220V/400V series), the Er13-1 alarm is reported.
The time interval from servo readiness to servo enabling can be user controlled.
Note 3: The servo enabling signal can be valid only when the RDY output signal is valid.
Note 4: The actual electric levels corresponding to valid I/O states can be set through P3.00–P3.15.
Powering-on
process
Main circuit
powered on
About 1.2s
Program
initialized
Note 1
Invalid
Invalid
Fan not run
Servo without output
Motor brake closed
Command input
invalid
-63-
Servo turning-on
process
Note 2
Note 3
Servo with output
≤100ms
Brake being
Motor brake released
released
200ms
Operating and running
Program started
running
Valid
Valid
Fan running
Note 4
Command
input valid