INVT DA180-S2R8SG0 Operation Manual page 70

Basic ac servo drive
Table of Contents

Advertisement

DA180 series basic AC servo drive
5.1.9.2 Timing sequence for power-off during running
Main power
PWM output
Servo readiness
output (RDY)
Microcontroller
state
Fan signal
Electromagnetic
brake release
signal output
(BRK)
Note 1: If main circuit voltage is less than 170V/330V(for 220V/400V series), the
undervoltage fault occurs and the electrical level of the servo fault (ALM) output increases.
Note 2: If the drive temperature is less than 45 ° C, the fan stops. If the IGBT temperature is
higher than 45 ° C, the fan stops after the microprocessor stops.
Note 3: The output delay of the electromagnetic brake release signal can be set through
P3.57. If the speed slows down under the setting of P3.58 (30r/min by default) during the
time specified by P3.57, the BRK signal becomes invalid.
Note 4: The actual electrical levels corresponding to valid I/O states can be set through
P3.00–P3.15.
5.1.9.3 Timing sequence for servo turning off in locked state
Servo enabling (SON)
Servo fault output
(ALM)
Servo readiness
output (RDY)
Dynamic brake
state
Electromagnetic
brake release
signal output
(BRK)
PWM output
Note 1: Whether to immediately start the dynamic brake can be set through P4.30.
Note 2: The servo locking time after braking can be set through P3.56.
Note 3: The actual electrical levels corresponding to valid I/O states can be set through
P3.00
P3.15.
Note 1
Servo with output
Valid
Program running
Note 2
Fan running
Motor brake
released
Note 3
Enabled
Dynamic brake
Note 1
switched off
Motor brake released
Note 2
Servo with output
-64-
Operating and running
Main circuit power lost
Servo without output
Invalid
Program stopped running
Fan stopped running
Motor brake closed
Disabled
No fault alarm
Normal
Dynamic brake switched on
Motor brake closed
Servo without output
Note 4