DA180 series basic AC servo drive
Code
Name
SDO sub-index not
Er26-2
exist
Incorrect SDO data
Er26-3
length
Er26-4 SDO data out of range
Modification not
Er26-5
allowed for read-only
Incorrect PDO
Er26-6
mapping length
PDO mapping data
Er26-7
not exist
PDO modification not
Er26-8
allowed in operational
state
PDO mapping not
Er26-9
allowed
Synchronization signal
Er26-a
too fast
Possible cause
dictionary or is not supported
by the servo drive.
When the SDO reads or
writes parameters, the index
exists in the object dictionary,
but the sub-index does not
exist in the dictionary or is
not supported by the servo
drive.
The length information in
SDO
read
or
commands does not match
the data length in the servo
drive object dictionary.
The data that the SDO writes
exceeds the data range in
the
servo
drive
dictionary.
There are attempts to modify
read-only parameters.
The total length of data
mapped
from
the
exceeds 64 bits.
The parameters associated
with the data mapped from
the PDO are not found in the
object dictionary.
There are attempts to modify
PDO mappings.
There are attempts to map
parameters
that
mapping to the PDO.
In synchronization working
mode, the number of frames
received by a slave node
exceeds the range supported
-270-
Check the index and sub-index on
the master node and on the servo
drive. Modify the index and sub-index
in the EDS file.
Adjust the length in SDO read or
write
write commands according to the
data length in the servo drive object
dictionary.
Adjust the size of data written by the
SDO according to the data range in
object
the object dictionary.
Eliminate the condition for making
the attempts to modify read-only
parameters.
PDO
Correct the length settings.
Ensure the PDO mapping index and
sub-index
dictionary.
Switch the CANopen status machine
to pre-operational and then modify
PDO mappings.
Ensure there are no read-only PDO
disallow
parameters that are mapped to the
RPDO.
1. Modify the time interval for the
master
node to
synchronization frames.
2. Change the baud rate.
Fault handling
Workaround
exist
in
the
object
send
data
or