ABB IRB 7600 - 500/2.55 Product Manual page 379

Articulated robot
Hide thumbs Also See for IRB 7600 - 500/2.55:
Table of Contents

Advertisement

Step 2 - Storing the revolution counter setting with the TPU
This section details the second step when updating the revolution counter; storing the
revolution counter setting with the TPU (RobotWare 4.0).
3HAC022033-001 Revision: E
Action
1. Press the button "Miscellaneous" then ENTER to select the service
window.
xx0100000194
2. Select Calibration from the View menu.
The Calibration window appears.
If there is more than one unit connected to the robot, they will be listed
in the window.
xx0100000201
3. Select the desired unit and choose Rev Counter Update from the
Calib menu.
The Revolution Counter Update window appears.
xx0100000202
4. Select the desired axis and press Incl to include it (it will be marked
with an x) or press All to select all axes.
5. Press OK when all axes that are to be updated are marked with an x.
CANCEL returns to the Calibration window.
6. Press OK again to confirm and start the update.
CANCEL returns to the Revolution Counter Update window.
7. At this point, it is recommended that the revolution counter values are
saved to a diskette.
5 Calibration information
5.5. Updating revolution counters
Note
Not required.
Continues on next page
Continued
377