Bit
Motor temperature status word faults/alarms
No.
0
1 = Motor temperature measurement fault active
F07011
[8016.8]
1
1 = Motor temperature model fault active
2
1 = Encoder temperature measurement fault active
3
Reserved
A07910
[8016.8]
4
1 = Motor temperature measurement alarm active
[8016.8]
5
1 = Motor temperature measurement alarm active
[8017.7]
6
Reserved
[8019.7]
<4>
7
Reserved
8
1 = Current reduction active
A07910
[8016.8]
9...15
Reserved
Mot temp_sensor
p0600[M]
from mot temp model 2
0
[8018.8]
from encoder 1
1
[4704.8]
from encoder 2
2
[4704.8]
from encoder 3
3
[4704.8]
from Motor Modules
11
or CUA31
Mot temp S_src 2 [°C]
20
p0608[0...3]
(0)
e. g. r4105 from TM120
Mot temp S_src 3 [°C]
21
p0609[0...3]
(0)
e. g. r4105 from TM120
Mot Temp S_src [°C]
p0603
10
[9576.7]
(0)
e. g. r4105 from TM31
[8018.1]
<1> For KTY, PT100, PT1000 and PTC, the value p0606 = 0 has a different meaning:
KTY, PT100, PT1000: 0
The output of the timer is always switched out (logical 0)
PTC: 0
Delay time = 0 s
<2> The switch-in delay p0607 = 0 suppresses fault F07016.
<3> For KTY, PT100, PT1000 and "No sensor", temperature as defined in the model.
<4> Motor temperature model 1/3: A07012, Motor temperature model 2: A07910
<5> Only for p0610 = 1.
1
2
DO: SERVO, VECTOR
Signals and monitoring functions - Thermal monitoring motor, Mot_temp ZSW F/A
Mot_temp ZSW F/A
r5389
r5389
MAX
1
<5>
<10>
r4620[0]
r4620[1]
r4620[2]
Mot temp_sens type
p0601[M]
Temperature channel
Temp_sens type
0 = No sensor
1
2
3
1 = PTC alarm & timer
p4600[E]
p4601[E] p4602[E] p4603[E]
2 = KTY84
r4620[0]
r4620[1]
r4620[2]
3 = KTY84 & PTC <8>
Temperature channel
4 = Bimetallic NC
contact alarm &
Temp_sens type
timer (only for
1
2
temp. evaluation
p4610[M]
p4611[M] p4612[M] p4613[M]
via MM)
5 = PT100 <9>
Configuration
6 = PT1000
7 = PT1000 and PTC
0 = No sensor
<8>
10 = PTC fault
Evaluation across
11 = PTC alarm
several temperature
12 = PTC alarm & timer
channels:
20 = KTY, PT100, PT1000
10 = SME12x
30 = Bimetallic NC contact fault
11 = BICO
31 = Bimetallic NC contact alarm
32 = Bimetallic NC contact alarm &
timer
<6> Applies only for VECTOR.
<7> p0606 does not work for alarms via p0616.
<8> Only for motors with DRIVE-CLiQ.
<9> p0601 = 5 can only be evaluated if r0192.15 = 1 and p0600 = 11; PT100 is calibrated via p0624.
<10> The assignment of temperature channels 1 … 4 depends on the hardware used.
<11> The relevant rated response temperature (°C) depends on the temperature sensor chosen by the motor manufacturer.
3
4
Mot_temp
r0035
Mod 1/2 threshold
p0605[M]
1
1
0
KTY/PT1000 sensor type
(threshold not applicable for PTC)
Mod 2/sens A_thr
p0604[M]
r4620[3]
M I N
4
1650
r4620[3]
PTC
<3>
sensor
type
3
4
-140 °C
250 °C
5
fp_8016_54_eng.vsd
07.01.16 V04.08.00
Mot temp response
p0610[M]
<6>
Fault response
&
Mot temp alarm 1
I_max reduction
&
p0616[M]
[6300.1], [6640.1]
Mod 2/sens timer
p0606[M]
<11>
<1>
<7>
F07011
T
0
&
"Motor overtemperature"
1
[8016.1]
[8017.8]
1
r2135.12
[8019.8]
A07910
1
"Motor overtemperature"
[8016.1]
0
Sensor fault time
1
p0607[M]
r2135.14
<2>
A07016
T
0
"Motor temperature
sensor fault"
A07015
"Motor temperature
sensor alarm"
A07820 "Temperature sensor not connected"
6
7
Function diagram
S120/S150/G130/G150
48 ms
p0610 = 1
Suppress fault
at p0610 = 0
[2548.2]
[2548.2]
8
- 8016 -