Lsu Control - ABB ACS880 Firmware Manual

Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

No.
Name / Range /
Selection
94

LSU control

94.1
LSU Control
Off
On
94.2
LSU panel
communication
Disable
Enable
94.4
INU-LSU status word
profile
ABB single drives
standard SW
Backwards
compatible SW
94.5
LSU external start
command
Description
Control of the supply unit of the drive, such as DC
voltage and reactive power reference.
Note that the references defined here must also be
selected as the reference source in the supply control
program to be effective.
This group is only visible when supply unit control has
been activated by parameter
1.
See also section Control of a supply unit (LSU) .
Enables/disables the internal INU-LSU state machine.
When the state machine is enabled, the inverter unit
(INU) controls the supply unit (LSU) and prevents the
inverter unit from starting until the supply unit is ready.
When the state machine is disabled, the status of the
supply unit is ignored by the inverter unit.
INU-LSU state machine disabled.
INU-LSU state machine enabled.
Enables/disables control panel and PC tool access to
the supply unit (line-side converter) via the inverter unit
(motor-side converter).
Note: This feature is only supported by the following
drives:
• ACS880-11
• ACS880-31
• ACS880-17 based on an integrated drive module
• ACS880-37 based on an integrated drive module.
Control panel and PC tool access to supply unit via
inverter unit disabled.
Control panel and PC tool access to supply unit via
inverter unit enabled.
(Only visible with certain drive types.)
Selects the functionality of bit 1 of
word.
The drive sets bit 1 of
6.11 Main status word
DC link is charged.
The drive sets bit 1 of
6.11 Main status word
main contactor is closed and the supply unit (line-side
converter) is running.
This setting can be used eg. when installing the drive
into an existing set-up with other ACS880 as well as
ACS800 drives.
(Only visible when IGBT supply unit control activated
by
)
95.20
Selects the source for LSU external start command.
This parameter is visible only if INU-ISU communication
is enabled in 92.20 bit 15.
Note: If LSU is stopped using parameter
external start
command, LSU continues to run during
the time defined by
94.11 LSU stop
95.20 HW options word
6.11 Main status
after the
after the
94.5 LSU
delay.
Parameters 589
Def / Type
FbEq 16b / 32b
On / uint16
0
1
Disable / uint16
0
1
ABB single drives
standard SW / uint16
0
1
Not selected / uint32