ABB ACS880 Firmware Manual page 306

Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

306 Parameters
No.
Name / Range /
Selection
22.41
Speed ref safe
-30000.00 ...
30000.00 rpm
22.42
Jogging 1 ref
-30000.00 ...
30000.00 rpm
22.43
Jogging 2 ref
-30000.00 ...
30000.00 rpm
22.51
Critical speed
function
b0
Enable
b1
Sign mode
b2...15
Reserved
0000h...FFFFh
22.52
Critical speed 1 low
-30000.00 ...
30000.00 rpm
22.53
Critical speed 1 high
-30000.00 ...
30000.00 rpm
Description
Defines a safe speed reference value that is used with
supervision functions such as
12.3 AI supervision function
49.5 Communication loss action
50.2 FBA A comm loss func
50.32 FBA B comm loss func
58.14 Communication loss
Safe speed reference. For scaling, see parameter 46.1.
Defines the speed reference for jogging function 1. For
more information on jogging, see page 99.
Speed reference for jogging function 1. For scaling, see
parameter 46.1.
Defines the speed reference for jogging function 2. For
more information on jogging, see page 99.
Speed reference for jogging function 2. For scaling, see
parameter 46.1.
Enables/disables the critical speeds function. Also
determines whether the specified ranges are effective
in both rotating directions or not.
See also section
Critical speeds/frequencies (page
1 = Enable: Critical speeds enabled.
0 = Disable: Critical speeds disabled.
1 = Signed: The signs of parameters
taken into account.
0 = Absolute: Parameters
absolute values.
Each range is effective in both directions of rotation.
Defines the low limit for critical speed range 1.
Note: This value must be less than or equal to the value
of
22.53 Critical speed 1
Low limit for critical speed 1. For scaling, see parameter
46.1.
Defines the high limit for critical speed range 1.
Note: This value must be greater than or equal to the
value of
22.52 Critical speed 1
High limit for critical speed 1. For scaling, see parameter
46.1.
action.
22.52...22.57
22.52...22.57
are handled as
high.
low.
Def / Type
FbEq 16b / 32b
- / real32
- / -
0.00 rpm / real32
- / -
0.00 rpm / real32
- / -
- / uint16
85).
are
1 = 1
0.00 rpm / real32
- / -
0.00 rpm / real32
- / -

Hide quick links: