ABB ACS880 Firmware Manual page 676

Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

676 Fault tracing
Code
Event name /
(hex)
Aux. code
A5EB
PU board
powerfail
A5EC
PU
communication
internal
A5ED
Measurement
circuit ADC
A5EE
Measurement
circuit DFF
A5EF
PU state
feedback
A5F0
Charging
feedback
A5F3
Switching
frequency
below
requested
A5F4
Control unit
battery
A682
Flash erase
speed
exceeded
A683
Data saving
to power unit
0, 1
2
A684
SD card
Cause
Power unit power supply failure.
Communication errors detected
between the drive control unit and the
power unit.
Problem with measurement circuit of
power unit (analog to digital
converter).
Problem with current or voltage
measurement of power unit.
State feedback from output phases
does not match control signals.
Charging in progress.
Adequate motor control at requested
output frequency cannot be reached
because of limited switching
frequency (eg. by parameter 95.15).
The battery of the control unit is low.
The flash memory (in the memory unit)
has been erased too frequently,
compromising the lifetime of the
memory.
An error in saving data to the power
unit.
An error is preventing saving from
initializing.
Write error.
Error related to SD card used to store
data (BCU control unit only).
What to do
Contact your local ABB representative.
Check the connections between the
drive control unit and the power unit.
Contact your local ABB representative.
Contact your local ABB representative.
Contact your local ABB representative.
Informative warning. Wait until
charging finishes before starting the
inverter unit.
Informative warning.
Replace control unit battery.
This warning can be suppressed using
parameter 31.40.
Avoid forcing unnecessary parameter
saves by parameter
96.7
parameter writes (such as user logger
triggering through parameters).
Check the auxiliary code (format XYYY
YZZZ). "X" specifies the source of
warning (1: generic flash erase
supervision). "ZZZ" specifies the flash
subsector number that generated the
warning.
Check the auxiliary code. See actions
for each code below.
Cycle the power to the drive. If the
control unit is externally powered,
also reboot the control unit (using
parameter
96.8 Control board
or by cycling its power. If the
problem persists, contact your local
ABB representative.
Cycle the power to the drive. If the
control unit is externally powered,
also reboot the control unit (using
parameter
96.8 Control board
or by cycling its power. If the
problem persists, contact your local
ABB representative.
Check the auxiliary code. See actions
for each code below.
or cyclic
boot)
boot)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents