408 Parameters
No.
Name / Range /
Selection
100...10000 s
35.56
Motor overload
action
No action
Warning only
Warning and fault
35.57
Motor overload class
Class 5
Class 10
Class 20
Class 30
Class 40
35.60
Cable temperature
0.0 ... 200.0 %
35.61
Cable nominal
current
0.00 ... 10000.00 A
Description
Motor thermal time constant.
Selects the action taken when motor overload is
detected.
See section
Motor overload protection (page
No action taken.
Drive generates warning
the motor is overloaded to the warning level, that is,
parameter
35.5 Motor overload level
88.0%.
Drive generates warning
the motor is overloaded to the warning level, that is,
parameter
35.5 Motor overload level
88.0%.
Drive trips on fault
7122 Motor overload
is overloaded to the fault level, that is, parameter
Motor overload level
reaches value 100.0%.
Defines the motor overload class to be used. The class
of protection is specified by the user as the time for
tripping at 7.2 times (IEC 60947-4-1) or 6 times (NEMA
ICS) the tripping level current.
See section
Motor overload protection (page
Motor overload class 5.
Motor overload class 10.
Motor overload class 20.
Motor overload class 30.
Motor overload class 40.
Shows the calculated temperature of the motor cable.
See section
Thermal protection of motor
cable (page
133).
102% = overtemperature warning
overload)
106% = overtemperature fault
overload)
This parameter is read-only.
Calculated temperature of motor cable.
Specifies the continuous current of the motor cable
for the thermal protection function in the control
program.
WARNING!
The value entered in this parameter must be
limited according to all factors affecting the
loadability of the cable, such as ambient
temperature, cabling arrangement, and
shrouding. Refer to the technical data from the
cable manufacturer.
Continuous current-carrying capacity of motor cable.
132).
A783 Motor overload
when
reaches value
A783 Motor overload
when
reaches value
when the motor
132).
(A480 Motor cable
(4000 Motor cable
Def / Type
FbEq 16b / 32b
1 = 1 s / 1 = 1 s
No action / uint16
0
1
2
35.5
Class 20 / uint16
0
1
2
3
4
0.0 % / real32
1 = 1 % / 10 = 1 %
10000.00 A / real32
1 = 1 A / 100 = 1 A