214 Parameters
No.
Name / Range /
Selection
10.13
DI5 ON delay
0.0 ... 3000.0 s
10.14
DI5 OFF delay
0.0 ... 3000.0 s
10.15
DI6 ON delay
0.0 ... 3000.0 s
10.16
DI6 OFF delay
0.0 ... 3000.0 s
10.21
RO status
10.24
RO1 source
Not energized
Energized
Ready run
Enabled
Description
Defines the activation delay for digital input DI5.
*DI status
**Delayed
DI status
t
t
On
Off
t
=
10.13 DI5 ON delay
On
t
=
10.14 DI5 OFF delay
Off
*Electrical status of digital input. Indicated by
status.
**Indicated by
10.2 DI delayed
Activation delay for DI5.
Defines the deactivation delay for digital input DI5. See
parameter
10.13 DI5 ON
Deactivation delay for DI5.
Defines the activation delay for digital input DI6.
*DI status
**Delayed
DI status
t
t
On
Off
t
=
10.15 DI6 ON delay
On
t
=
10.16 DI6 OFF delay
Off
*Electrical status of digital input. Indicated by
status.
**Indicated by
10.2 DI delayed
Activation delay for DI6.
Defines the deactivation delay for digital input DI6. See
parameter
10.15 DI6 ON
Deactivation delay for DI6.
Status of relay outputs RO8...RO1. Example: 00000001b
= RO1 is energized, RO2...RO8 are de-energized.
Selects a drive signal to be connected to relay output
RO1.
Output is not energized.
Output is energized.
Bit 1 of
6.11 Main status word (page
Bit 0 of
6.16 Drive status word 1 (page
t
t
Off
On
status.
delay.
t
t
On
Off
status.
delay.
192).
192).
Def / Type
FbEq 16b / 32b
0.0 s / uint32
1
0
1
0
Time
10.1 DI
10 = 1 s / 10 = 1 s
0.0 s / uint32
10 = 1 s / 10 = 1 s
0.0 s / uint32
1
0
1
0
Time
10.1 DI
10 = 1 s / 10 = 1 s
0.0 s / uint32
10 = 1 s / 10 = 1 s
- / uint16
Ready run; 10.01 b3
(-1) (95.20 b2); 35.105
b1 (95.20 b6); 06.16
b6 (95.20 b9) / uint32
0
1
2
4