ABB ACS880 Firmware Manual page 348

Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

348 Parameters
No.
Name / Range /
Selection
Motor
potentiometer
PID
Control panel (ref
saved)
Control panel (ref
copied)
Other [value]
28.12
Frequency ref2
source
28.13
Frequency ref1
function
Ref1
Add (ref1 + ref2)
Sub (ref1 - ref2)
Mul (ref1 x ref2)
Min (ref1, ref2)
Max (ref1, ref2)
28.14
Frequency ref1/2
selection
Frequency reference
1
Frequency reference
2
Follow Ext1/Ext2
selection
DI1
DI2
DI3
Description
40.1 Process PID output actual
PID controller).
Control panel reference, with initial value from last-used
panel reference. See section
an external control source (page
Control panel reference, with initial value from previous
source or actual value. See section
panel as an external control source (page
See
Terms and abbreviations (page
Selects frequency reference source 2.
For the selections, and a diagram of reference source
selection, see parameter
Selects a mathematical function between the reference
sources selected by parameters
source
and
28.12 Frequency ref2
at
28.11 Frequency ref1
Signal selected by
28.11 Frequency ref1 source
as frequency reference 1 as such (no function applied).
The sum of the reference sources is used as frequency
reference 1.
The subtraction
([28.11 Frequency ref1
Frequency ref2
source]) of the reference sources is used
as frequency reference 1.
The multiplication of the reference sources is used as
frequency reference 1.
The smaller of the reference sources is used as
frequency reference 1.
The greater of the reference sources is used as
frequency reference 1.
Configures the selection between frequency references
1 and 2. See diagram at
0 = Frequency reference 1
1 = Frequency reference 2
0.
1.
Frequency reference 1 is used when external control
location EXT1 is active. Frequency reference 2 is used
when external control location EXT2 is active.
See also parameter
19.11 Ext1/Ext2
Digital input DI1
(10.2 DI delayed
Digital input DI2
(10.2 DI delayed
Digital input DI3
(10.2 DI delayed
(output of the process
Using the control panel as
41).
Using the control
41).
169).
28.11 Frequency ref1
28.11 Frequency ref1
source. See diagram
source.
source] -
28.11 Frequency ref1
source.
selection.
status, bit 0).
status, bit 1).
status, bit 2).
Def / Type
FbEq 16b / 32b
15
16
18
19
P.9.21 / uint32
source.
Ref1 / uint16
is used
0
1
[28.12
2
3
4
5
Follow Ext1/Ext2
selection / uint32
0
1
2
3
4
5