No.
Name / Range /
Selection
31.35
Main fan fault
function
Fault
Warning
No action
31.36
Aux fan fault
function
Fault
Warning
Description
Selects how the drive reacts when a main cooling fan
fault is detected.
Note: With an inverter unit consisting of one or more
frame R8i inverter modules with speed-controlled fans,
it may be possible to continue operation even if one
main fan of a module stops. When fan failure is
detected, the control program will automatically
set the other fan of the module to full speed
set the fans of the other modules (if any) to full
speed
decrease the switching frequency to a minimum,
and
disable the supervision of temperature difference
between the modules.
If this parameter is set to Fault, the inverter unit will
trip (but still carry out the actions listed above).
Otherwise, the inverter will attempt to continue
operation.
The drive trips on fault
The drive generates an
No action taken.
(Only visible with a ZCU control unit)
Selects how the drive reacts when a modules internal
auxiliary fan fault is detected.
The drive trips on fault
Note: The fault is suppressed for two minutes after
power-up.
During this time, the drive only generates a warning,
A582 Auxiliary fan not
The drive generates a warning,
running.
5080
Fan.
A581
Fan.
5081 Auxiliary fan not
running.
A582 Auxiliary fan not
Parameters 375
Def / Type
FbEq 16b / 32b
Warning / uint16
0
1
2
Fault / uint16
running.
0
1