ABB ACS880 Firmware Manual page 689

Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

Code
Event name /
(hex)
Aux. code
A8C0
Fan service
counter
A981
External
warning 1
A982
External
warning 2
A983
External
warning 3
A984
External
warning 4
A985
External
warning 5
AF80
INU-LSU
comm loss
AF85
Line side unit
warning
AF8C
Process PID
sleep mode
AF90
Speed
controller
autotuning
0000
0001
Cause
A cooling fan has reached the end of
its estimated lifetime.
See parameters
5.41
and 5.42.
Fault in external device 1.
Fault in external device 2.
Fault in external device 3.
Fault in external device 4.
Fault in external device 5.
DDCS (fiber optic) communication
between converters (for example, the
inverter unit and the supply unit) is
lost.
Note that the inverter unit will
continue operating based on the
status information that was last
received from the other converter.
The supply unit (or other converter)
has generated a warning.
The drive is entering sleep mode.
The speed controller autotune routine
did not complete successfully.
The drive was stopped before the
autotune routine finished.
The drive was started but was not
ready to follow the autotune
command.
Fault tracing 689
What to do
Check the auxiliary code. The code
indicates which fan is to be replaced.
0: Main cooling fan
1: Auxiliary cooling fan
2: Auxiliary cooling fan 2
3: Cabinet cooling fan
4: PCB compartment fan
Refer to the hardware manual of the
drive for fan replacement instructions.
Check the external device.
Check setting of parameter
External event 1
source.
Check the external device.
Check setting of parameter
External event 2
source.
Check the external device.
Check setting of parameter
External event 3
source.
Check the external device.
Check setting of parameter
External event 4
source.
Check the external device.
Check setting of parameter
External event 5
source.
Check status of other converter
(parameters 6.36 LSU Status Word and
6.39 Internal state machine LSU CW ).
Check settings of parameter group
DDCS
communication. Check the
corresponding settings in the control
program of the other converter.
Check cable connections. If necessary,
replace cables.
The auxiliary code specifies the
original warning code in the supply
unit control program. See section
Auxiliary codes for line-side converter
warnings (page
697).
Informative warning. See section
Process PID
control, and parameters
40.41...40.48.
Check the auxiliary code (format XXXX
YYYY). "YYYY" indicates the problem
(see actions for each code below).
Repeat autotune until successful.
Make sure the prerequisites of the
autotune run are fulfilled. See
section
Speed controller
autotune (page
87).
31.1
31.3
31.5
31.7
31.9
60