Name / Range /
Selection
0000h...FFFFh
31.42
Overcurrent fault
limit
0.00 ... 30000.00 A
31.54
Fault action
Coast
Emergency ramp
31.55
Ext I/O comm loss
event
No action
Warning
Fault
31.200
Sync loss status
word
b0
Triggered
b1
Triggered as
warning
b2
Triggered as fault
b3
Function enabled
b4
Frequency above
detection limit
b5
Cos phi below
minimum
b6
Cos phi drop
detected
b7...15
Reserved
0000h...FFFFh
Description
Sets a custom motor current fault limit.
The drive automatically sets an internal motor current
limit according to the drive hardware. The internal limit
is appropriate in most cases, but this parameter can
be used to set a lower current limit, for example, to
protect a permanent magnet motor from
demagnetization.
Note: The limit defines the maximum peak current of
one phase.
With this parameter at 0.0 A, only the internal limit is
in force.
Custom motor current fault limit. For scaling, see
parameter 46.5.
Selects the stop mode when a non-critical fault occurs.
The drive coasts to a stop.
The drive follows the ramp specified for an emergency
stop in parameter
23.23 Emergency stop
Selects how the drive reacts when the communication
to an I/O extension module fails.
No action taken.
The drive generates a warning,
The drive trips on a fault,
Shows the status bits for sync loss supervision activity.
1 = Sync loss condition is detected.
1 = Sync loss condition is detected and
sync
warning is triggered.
1 = Sync loss condition is detected and
fault is triggered.
1 = Supervision function is enabled and condition of
cos phi signal is monitored.
1 = Drive output value is above the value defined in
parameter
31.202 Sync loss minimum detection
1 = Actual cos phi value is below the value defined in
parameter
31.206 Sync loss cos phi minimum
1 = Cos phi value has dropped more than or is equal to
the limit defined by parameter 31.205.
time.
A799 ExtIO comm
7082 Ext I/O comm
loss.
D213 Out of
D113 Out of sync
level.
Parameters 377
Def / Type
FbEq 16b / 32b
1 = 1
0.00 A / real32
- / -
Coast / uint16
0
1
Fault / uint16
0
loss.
1
2
- / uint16
limit.
1 = 1