ABB ACS880 Firmware Manual page 402

Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

402 Parameters
No.
Name / Range /
Selection
35.21
Temperature 2
source
Disabled
Estimated
temperature
KTY84 analog I/O
KTY84 encoder
module 1
KTY84 encoder
module 2
Description
Selects the source from which measured temperature
2 is read.
For wiring examples, see the hardware manual of the
drive.
Usually this source is from a sensor connected to the
motor controlled by the drive, but it could be used to
measure and monitor a temperature from other parts
of the process as long as a suitable sensor is used as
per the selection list.
None. Temperature monitoring function 2 is disabled.
Estimated motor temperature (see parameter
Motor estimated
temperature).
The temperature is estimated from an internal drive
calculation. It is important to set up the ambient
temperature of the motor in
temperature.
KTY84 sensor connected to the analog input selected
by parameter
35.24 Temperature 2 AI source
analog output. The input and output can be on the drive
control unit or on an extension module.
The following settings are required:
Set the hardware jumper or switch related to the
analog input to U (voltage). Any change must be
validated by a control unit reboot.
Set the unit selection parameter of the input to
volt.
Set the source selection parameter of the analog
output to
"Force KTY84
Select the analog input in parameter 35.24. In case
the input is located on an I/O extension module,
use the selection Other (see
abbreviations (page
input value parameter (for example,
actual
value).
The analog output feeds a constant current through
the sensor. As the resistance of the sensor changes
along with its temperature, the voltage over the sensor
changes. The voltage is read by the analog input and
converted into degrees.
KTY84 sensor connected to encoder interface 1.
See also parameters
91.21 Module 1 temp sensor type
and
91.22 Module 1 temp filter
KTY84 sensor connected to encoder interface 2.
See also parameters
91.24 Module 2 temp sensor type
and
91.25 Module 2 temp filter
35.1
35.50 Motor ambient
and an
excitation".
Terms and
20)) to point at the actual
14.26 AI1
time.
time.
Def / Type
FbEq 16b / 32b
Disabled / uint16
0
1
2
3
4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents