Code
Event name /
(hex)
Aux. code
0003
0004
0005
0006
0007
0008
0009
3E00
Input phase
loss
4000
Motor cable
overload
4100
Ambient
temperature
4110
Control board
temperature
4210
IGBT
overtemperature
Cause
Too much difference between
measured and estimated positions.
Rotor did not rotate as expected
between zero pulses.
Position estimate did not stabilize.
Measured position status
information changed.
General autophasing failure.
Selected mode not supported.
(LV-Synchro) Standstill failure.
Input phase loss detected by the IGBT
bridge.
Calculated motor cable temperature
has exceeded warning limit.
Drive module temperature is
excessive.
Control board temperature is too high.
Estimated drive IGBT temperature is
excessive.
Fault tracing 657
What to do
Check that encoder is not slipping.
Check parameter
98.15
to verify that the autophasing
routine gives consistent results.
Check the motor model parameters.
Check that the zero pulses are given
correctly.
Check that the selected mode
(parameter 21.13) is appropriate for
the motor.
Check that parameter
changed to
Estimate
routine.
Contact your local ABB
representative.
Check that the selected mode
(parameter 21.13) is supported by
the motor type.
Contact your local ABB
representative.
Check the auxiliary code. Check the
source of the fault corresponding to
the code:
1: Phase A
2: Phase B
4: Phase C
8: Phase cannot be detected
Check the AC fuses.
Check for input power supply
imbalance.
Check the settings of parameters
35.61
and 35.62.
Check the dimensioning of the motor
cable in regard to required load.
Check ambient temperature. If it
exceeds 40 °C (104 °F), ensure that
load current does not exceed derated
load capacity of drive. See appropriate
Hardware manual .
Check drive module cooling air flow
and fan operation.
Check inside of cabinet and heatsink
of drive module for dust pick-up. Clean
whenever necessary.
Check proper cooling of the drive.
Check the auxiliary cooling fan.
Check ambient conditions.
Check air flow and fan operation.
Check heatsink fins for dust pick-up.
Check motor power against drive
power.
several times