Code
Event name /
(hex)
Aux. code
6591
Backup/Restore
Timeout
65A1
FBA A
parameter
conflict
65A2
FBA B
parameter
conflict
65B1
Reference
source
parametrization
6681
EFB
communication
loss
6682
EFB
configuration
file
6683
EFB invalid
parameterization
6684
EFB load fault
6881
Text data
overflow
6882
Text 32-bit
table overflow
6883
Text 64-bit
table overflow
6885
Text file
overflow
7080
Option
module comm
loss
7081
Control panel
loss
Cause
Parameter load or save timeout
caused by communication break
between drive and control panel, or
control panel and PC tool.
The drive does not have a functionality
requested by PLC, or requested
functionality has not been activated.
The drive does not have a functionality
requested by PLC, or requested
functionality has not been activated.
A reference source is simultaneously
connected to multiple parameters
with different units.
Communication break in embedded
fieldbus (EFB) communication.
Embedded fieldbus (EFB)
configuration file could not be read.
Embedded fieldbus (EFB) parameter
settings inconsistent or not
compatible with selected protocol.
Embedded fieldbus (EFB)
protocol firmware could not be
loaded.
Version mismatch between EFB
protocol firmware and drive
firmware.
Internal fault.
Internal fault.
Internal fault.
Internal fault.
Communication between drive and an
option module is lost.
Control panel (or PC tool) has stopped
communicating.
Fault tracing 665
What to do
Check the communication between
drive and control panel or PC. Retry.
Check PLC programming.
Check settings of parameter groups
50 Fieldbus adapter (FBA)
A
settings.
Check PLC programming.
Check settings of parameter groups
50 Fieldbus adapter (FBA)
B
settings.
See
A6DA Reference source
parametrization (page
Check the status of the fieldbus
master (online/offline/error etc.).
Check cable connections to the XD2D
connector on the control unit.
Contact your local ABB representative.
Check the settings in parameter group
58 Embedded
fieldbus.
Contact your local ABB representative.
Reset the fault. Contact your local ABB
representative if the fault persists.
Reset the fault. Contact your local ABB
representative if the fault persists.
Reset the fault. Contact your local ABB
representative if the fault persists.
Reset the fault. Contact your local ABB
representative if the fault persists.
See
A798 Encoder option comm
loss (page
681).
Check PC tool or control panel
connection.
Check control panel connector.
Disconnect and reconnect the control
panel.
and
51 FBA
and
54 FBA
678).