554 Parameters
No.
Name / Range /
Selection
DIO2
ESP CW bit 12
Other [bit]
81.19
Time trigger
0.00 ... 650.00 hour
81.20
Number of cleaning
cycles
0...65000
81.21
First step reference
-300.00 ... 300.00%
81.22
First step time
0.0 ... 6500.0 s
81.23
Off time
0.0 ... 6500.0 s
81.24
Second step
reference
-300.00 ... 300.00%
81.25
Second step time
0.0 ... 6500.0 s
81.31
Cleaning acc time
0.00 ... 30000.00 s
81.32
Cleaning dec time
Description
Digital input/output DIO2
1).
Parameter
74.1 ESP control word (page
controls enable/disable status of the function.
See
Terms and abbreviations (page
Defines time setting for periodic cleaning schedule.
When parameter
81.81 Since last cleaning
reaches the value set in this parameter, the cleaning
request is automatically generated.
After cleaning operation is completed, the timer is then
reset for another round with parameter
cleaning
which displays remaining time till the next
cleaning request based on this parameter time setting.
Note: For the time trigger to work, parameter
Pump cleaning option
Time trigger in hours.
Defines the desired quantity of cleaning cycles.
Each cycle consists of two speed steps with period of
off-time after each step. The period and dynamics of
each cycle are defined with parameters
reference...81.32.
Number of cleaning cycles.
Defines speed reference for the first step of cleaning
cycle.
Note that the parameter
is also taken into use for the cleaning operation.
First step reference in percentage.
Defines the time period for the first step of cleaning
cycle.
First step time in second.
Defines the time period for the pause after each step.
The speed reference will be zero during Off time.
Off time in seconds.
Defines speed reference for the second step of cleaning
cycle.
Note that the parameter
is also taken into use for the cleaning operation.
Second step reference in percentage.
Defines the time period for the second step of cleaning
cycle.
Second step time in seconds.
Defines acceleration time for the cleaning operation.
Cleaning acceleration time in seconds.
Defines deceleration time for the cleaning operation.
(11.2 DIO delayed
status, bit
519), bit 12 status
169).
time counter
81.82 Until next
sel, bit-2 must be set to 1.
81.21 First step
75.15 Starting speed
75.15 Starting speed
Def / Type
FbEq 16b / 32b
11
12
0.00 hour / real32
81.02
100 = 1 hour / 100 = 1
hour
1 / real32
1 = 1 / 1 = 1
-10.00% / real32
setting
100 = 1% / 100 = 1%
5.0 s / real32
10 = 1 s / 10 = 1 s
5.0 s / real32
10 = 1 s / 1 = 1 s
10.00% / real32
setting
10 = 1% / 100 = 1%
5.0 s / real32
10 = 1 s / 10 = 1 s
20.00 s / real32
1 = 1 s / 100 = 1 s
20.00 s / real32