368 Parameters
No.
Name / Range /
Selection
FBA A MCW bit 7
EFB MCW bit 7
Other [bit]
31.12
Autoreset selection
b0
Overcurrent
b1
Overvoltage
b2
Undervoltage
b3
AI supervision fault
b4
Supply unit
b5...7
Reserved
b8
Application fault 1
b9
Application fault 2
b10
Selectable fault
b11
External fault 1
b12
External fault 2
b13
External fault 3
b14
External fault 4
Description
Control word bit 7 received through fieldbus interface
A.
Control word bit 7 received through the embedded
fieldbus interface.
See
Terms and abbreviations (page
Selects faults that are automatically reset. The
parameter is a 16-bit word with each bit corresponding
to a fault type.
Whenever a bit is set to 1, the corresponding fault is
automatically reset.
The number and interval of reset attempts are defined
by parameters 31.14...31.16.
WARNING!
Before you activate the function, make sure that
no dangerous situations can occur. The function
resets the drive automatically and continues
operation after a fault.
Note:
The autoreset function is only available in external
control; see section
control (page
39).
Faults related to the Safe torque off (STO)
function cannot be automatically reset.
The bits of this binary number correspond to the
following faults:
Defined in the application program
Defined in the application program
See parameter
31.13 User selectable fault
From source selected by parameter
1 source
From source selected by parameter
2 source
From source selected by parameter
3 source
From source selected by parameter
4 source
169).
Local control vs. external
31.1 External event
31.3 External event
31.5 External event
31.7 External event
Def / Type
FbEq 16b / 32b
30
32
- / uint16