No.
Name / Range /
Selection
-22.000 ... 22.000 mA
or V
14.59
AI3 HW switch
position
mA
V
14.60
AI3 unit selection
mA
V
14.61
AI3 filter gain
No filtering
125 us
250 us
500 us
1 ms
2 ms
4 ms
7.9375 ms
Description
Forced value of analog input AI3.
(Visible when
14.1 Module 1 type
Shows the position of the hardware current/voltage
selector on the I/O extension module.
Note: The setting of the current/voltage selector must
match the unit selection made in parameter
unit
selection. I/O module reboot either by cycling the
power or through parameter
is required to validate any changes in the hardware
settings.
Milliamperes.
Volts.
(Visible when
14.1 Module 1 type
Selects the unit for readings and settings related to
analog input AI3.
Note: This setting must match the corresponding
hardware setting on the I/O extension module (see the
manual of the I/O extension module). The hardware
setting is shown by parameter
position. I/O module reboot either by cycling the power
or through parameter
required to validate any changes in the hardware
settings.
Milliamperes.
Volts.
(Visible when
14.1 Module 1 type
Selects a hardware filtering time for AI3.
See also parameter
14.62 AI3 filter
No filtering.
125 microseconds.
250 microseconds.
500 microseconds.
1 millisecond.
2 milliseconds.
4 milliseconds.
7.9375 milliseconds.
= FIO-11)
14.60 AI3
96.8 Control board boot
= FIO-11)
14.59 AI3 HW switch
96.8 Control board boot
= FIO-11)
time.
Parameters 255
Def / Type
FbEq 16b / 32b
1000 = 1 mA or V /
1000 = 1 mA or V
mA / uint16
10
2
mA / uint16
is
10
2
1 ms / uint16
0
1
2
3
4
5
6
7