228 Parameters
No.
Name / Range /
Selection
12.22
AI2 scaled value
-32768.000 ...
32767.000
12.25
AI2 unit selection
V
mA
12.26
AI2 filter time
0.000 ... 30.000 s
12.27
AI2 min
-22.000 ... 22.000 mA
or V
12.28
AI2 max
-22.000 ... 22.000 mA
or V
Description
Displays the value of analog input AI2 after scaling. See
parameters
12.29 AI2 scaled at AI2 min
scaled at AI2
max.
This parameter is read-only.
Scaled value of analog input AI2.
Selects the unit for readings and settings related to
analog input AI2.
Note: This setting must match the corresponding
hardware setting on the drive control unit (see the
hardware manual of the drive). Control board reboot
(either by cycling the power or through parameter
Control board
boot) is required to validate any changes
in the hardware settings.
Volts.
Milliamperes.
Defines the filter time constant for analog input AI2.
See parameter
12.16 AI1 filter
Filter time constant.
Defines the minimum site value for analog input AI2.
Set the value actually sent to the drive when the analog
signal from plant is wound to its minimum setting.
See also parameter
12.1 AI
Minimum value of AI2.
Defines the maximum site value for analog input AI2.
Set the value actually sent to the drive when the analog
signal from plant is wound to its maximum setting.
See also parameter
12.1 AI
Maximum value of AI2.
and
12.30 AI2
time.
tune.
tune.
Def / Type
FbEq 16b / 32b
- / real32
1 = 1 / 1000 = 1
mA / uint16
96.8
2
10
0.100 s / real32
1000 = 1 s / 1000 = 1
s
0.000 mA or V /
real32
1000 = 1 mA or V /
1000 = 1 mA or V
20.000 mA or V /
real32
1000 = 1 mA or V /
1000 = 1 mA or V