304 Parameters
No.
Name / Range /
Selection
b2...15
Reserved
0000h...FFFFh
22.22
Constant speed sel1
Not selected
Selected
DI1
DI2
DI3
DI4
DI5
DI6
DIO1
DIO2
Other [bit]
Description
When bit 0 of parameter
is 0 (Separate), selects a source that activates constant
speed 1.
When bit 0 of parameter
is 1 (Packed), this parameter and parameters
Constant speed sel2
and
select three sources whose states activate constant
speeds as follows:
Source
Source
defined by
defined by
par.
22.22
par.
22.23
0
0
1
0
0
1
1
1
0
0
1
0
0
1
1
1
0
1
Digital input DI1
(10.2 DI delayed
Digital input DI2
(10.2 DI delayed
Digital input DI3
(10.2 DI delayed
Digital input DI4
(10.2 DI delayed
Digital input DI5
(10.2 DI delayed
Digital input DI6
(10.2 DI delayed
Digital input/output DIO1
0).
Digital input/output DIO2
1).
See
Terms and abbreviations (page
22.21 Constant speed function
22.21 Constant speed function
22.23
22.24 Constant speed sel3
Source
Constant
defined by
speed active
par.
22.24
0
None
0
Constant
speed 1
0
Constant
speed 2
0
Constant
speed 3
1
Constant
speed 4
1
Constant
speed 5
1
Constant
speed 6
1
Constant
speed 7
status, bit 0).
status, bit 1).
status, bit 2).
status, bit 3).
status, bit 4).
status, bit 5).
(11.2 DIO delayed
status, bit
(11.2 DIO delayed
status, bit
169).
Def / Type
FbEq 16b / 32b
1 = 1
DI5 / uint32
0
1
2
3
4
5
6
7
10
11