No.
Name / Range /
Selection
0.00 ... 3000.00 s
14.28
AI1 force data
-22.000 ... 22.000 mA
or V
14.28
DIO4 OFF delay
0.00 ... 3000.00 s
14.29
AI1 HW switch
position
mA
V
14.30
AI1 unit selection
mA
V
14.31
RO status
14.31
AI1 filter gain
No filtering
125 us
250 us
500 us
Description
Activation delay for DIO4.
(Visible when
14.1 Module 1 type
Forced value that can be used instead of the true
reading of the input. See parameter
selection.
Forced value of analog input AI1.
(Visible when
14.1 Module 1 type
Defines the deactivation delay for digital input/output
DIO4. See parameter
14.12 DIO1 ON
Deactivation delay for DIO4.
(Visible when
14.1 Module 1 type
Shows the position of the hardware current/voltage
selector on the I/O extension module.
Note: The setting of the current/voltage selector must
match the unit selection made in parameter
unit
selection. I/O module reboot either by cycling the
power or through parameter
is required to validate any changes in the hardware
settings.
Milliamperes.
Volts.
(Visible when
14.1 Module 1 type
Selects the unit for readings and settings related to
analog input AI1.
Note: This setting must match the corresponding
hardware setting on the I/O extension module (see the
manual of the I/O extension module). The hardware
setting is shown by parameter
position. I/O module reboot either by cycling the power
or through parameter
required to validate any changes in the hardware
settings.
Milliamperes.
Volts.
(Visible when
14.1 Module 1 type
Status of relay outputs on the I/O extension module.
Example: 0001b = RO1 is energized, RO2 is
de-energized.
(Visible when
14.1 Module 1 type
Selects a hardware filtering time for AI1.
See also parameter
14.32 AI1 filter
No filtering.
125 microseconds.
250 microseconds.
500 microseconds.
= FAIO-01)
14.22 AI force
= FIO-01)
delay.
= FAIO-01)
14.30 AI1
96.8 Control board boot
= FAIO-01)
14.29 AI1 HW switch
96.8 Control board boot
= FDIO-01)
= FAIO-01)
time.
Parameters 247
Def / Type
FbEq 16b / 32b
10 = 1 s / 100 = 1 s
- / real32
1000 = 1 mA or V /
1000 = 1 mA or V
0.00 s / real32
10 = 1 s / 100 = 1 s
mA / uint16
10
2
mA / uint16
is
10
2
- / uint16
1 ms / uint16
0
1
2
3

Hide quick links: