ABB ACS880 Firmware Manual page 245

Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

No.
Name / Range /
Selection
No action
AI1 min tune
AI1 max tune
AI2 min tune
AI2 max tune
AI3 min tune
AI3 max tune
14.21
DIO3 output source
14.22
AI force selection
b0
AI1
b1
AI2
b2...15
Reserved
0000h...FFFFh
14.22
DI3 ON delay
0.00 ... 3000.00 s
14.22
AI force selection
b0
AI1
Description
Tuning action completed or no action has been
requested.
The parameter automatically reverts to this value after
any tuning action.
The measured value of AI1 is set as the minimum value
of AI1 into parameter
14.33 AI1
The measured value of AI1 is set as the maximum value
of AI1 into parameter
14.34 AI1
The measured value of AI2 is set as the minimum value
of AI2 into parameter
14.48 AI2
The measured value of AI2 is set as the maximum value
of AI2 into parameter
14.49 AI2
The measured value of AI3 is set as the minimum value
of AI3 into parameter
14.63 AI3
The measured value of AI3 is set as the maximum value
of AI3 into parameter
14.64 AI3
(Visible when
14.1 Module 1 type
Selects a drive signal to be connected to digital
input/output DIO3 when parameter
is set to Output.
For the available selections, see parameter
output
source.
(Visible when
14.1 Module 1 type
The true readings of the analog inputs can be
overridden for eg. testing purposes. A forced value
parameter is provided for each analog input, and its
value is applied whenever the corresponding bit in this
parameter is 1.
1 = Force mode: Force AI1 to value of parameter
AI1 force
data.
1 = Force mode: Force AI2 to value of parameter
AI2 force
data.
(Visible when
14.1 Module 1 type
Defines the activation delay for digital input DI3. See
parameter
14.12 DI1 ON
Activation delay for DI3.
(Visible when
14.1 Module 1 type
The true readings of the analog inputs can be
overridden for eg. testing purposes. A forced value
parameter is provided for each analog input, and its
value is applied whenever the corresponding bit in this
parameter is 1.
1 = Force mode: Force AI1 to value of parameter
AI1 force
data.
min.
max.
min.
max.
min.
max.
= FIO-01)
14.19 DIO3 function
14.11 DIO1
= FAIO-01)
= FDIO-01)
delay.
= FIO-11)
Parameters 245
Def / Type
FbEq 16b / 32b
0
1
2
3
4
5
6
Not energized /
uint32
- / uint16
14.28
14.43
1 = 1
0.00 s / real32
10 = 1 s / 100 = 1 s
- / uint16
14.28

Hide quick links: