596 Parameters
No.
Name / Range /
Selection
0...65535
95.14
Connected modules
b0
b1
b2
b3
b4
b5
b6
b7
b8
b9
b10
b11
b12...15
Reserved
0000h...FFFFh
95.15
Special HW settings
b0
EX motor
b1
ABB sine filter
b2
High speed mode
Description
Number of inverter modules available.
(Only visible with a BCU control unit)
Shows which of the parallel-connected inverter modules
have been detected by the control program.
Note: This parameter is read-only.
Module 1 has been detected.
Module 2 has been detected.
Module 3 has been detected.
Module 4 has been detected.
Module 5 has been detected.
Module 6 has been detected.
Module 7 has been detected.
Module 8 has been detected.
Module 9 has been detected.
Module 10 has been detected.
Module 11 has been detected.
Module 12 has been detected.
Contains hardware-related settings that can be enabled
and disabled by toggling the specific bits.
Note: The installation of the hardware specified by this
parameter may require derating of drive output, or
impose other limitations. Refer to the hardware manual
of the drive.
Note: This parameter cannot be changed while the
drive is running.
1 = The driven motor is an Ex motor provided by ABB
for potentially explosive atmospheres. This sets the
required minimum switching frequency for ABB Ex
motors.
Note: For non-ABB Ex motors, contact your local ABB
representative.
1 = An ABB sine filter is connected to the output of the
drive/inverter.
1 = Minimum switching frequency limit adaptation to
output frequency active. This setting improves control
performance at high output frequencies (typically
above 120 Hz.
Def / Type
FbEq 16b / 32b
- / -
- / uint16
1 = 1
- / uint16