No.
Name / Range /
Selection
Pt1000 encoder
module 2
35.12
Temperature 1 fault
limit
-60...1000 °
35.13
Temperature 1
warning limit
-60...1000 °
35.14
Temperature 1 AI
source
Not selected
AI1 actual value
AI2 actual value
Other [value]
35.17
Temperature 1
calibration
-30...1000 °
Description
Pt1000 sensor connected to encoder interface 2. See
parameters
91.24 Module 2 temp sensor type
Module 2 temp filter
time.
Note: Pt1000 sensor supports FEN-11 and FEN-31
encoder modules only.
Defines the fault limit for temperature monitoring
function 1.
When measured temperature 1 exceeds the limit, the
drive trips on fault
4981 External temperature
The unit is selected by parameter
Note: With °F, the range is -76...1832. With a PTC sensor,
the range is 0...5000 ohms.
Fault limit for temperature monitoring function 1.
Defines the warning limit for temperature monitoring
function 1. When measured temperature 1 exceeds this
limit, a warning
(A491 External temperature
generated.
The unit is selected by parameter
Note: With °F, the range is -76...1832. With a PTC sensor,
the range is 0...5000 ohms.
Warning limit for temperature monitoring function 1.
Specifies the analog input when the setting of
Temperature 1 source
an analog input.
Note: If the input is located on an I/O extension module,
use the selection Other to point to the AI actual value
in group 14, 15 or 16, eg.
None.
Analog input AI1 on the control unit.
Analog input AI2 on the control unit.
See
Terms and abbreviations (page
Defines the calibration of temperature 1.
Calibration can be used to fine-tune the motor
temperature measurement. Once the motor has cooled
down, measure its ambient temperature and set this
value accordingly.
This parameter affects only if Pt100 or Pt1000
measurement is using AI and AO of the control unit or
I/O extension modules.
Calibration of temperature 1 in celsius.
96.16 Unit
selection.
1) is
96.16 Unit
selection.
requires measurement through
14.26 AI1 actual
value.
169).
Parameters 401
Def / Type
FbEq 16b / 32b
17
and
91.25
130 ° / real32
1.
1 = 1 ° / 1 = 1 °
110 ° / real32
1 = 1 ° / 1 = 1 °
35.11
Not selected / uint32
0
1
2
0 ° / real32
1 = 1 ° / 1 = 1 °