ABB ACS880 Firmware Manual page 487

Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

No.
Name / Range /
Selection
b2
Local
b3...15
Reserved
0000h...FFFFh
58.101
Data I/O 1
None
CW 16bit
Ref1 16bit
Ref2 16bit
SW 16bit
Act1 16bit
Act2 16bit
CW 32bit
Ref1 32bit
Ref2 32bit
SW 32bit
Act1 32bit
Act2 32bit
CW2 16bit
SW2 16bit
RO/DIO control
word
AO1 data storage
AO2 data storage
Feedback data
storage
Setpoint data
storage
Other [value]
Description
1 = Communication monitoring active when local
control is being used.
Defines the address in the drive which the Modbus
master accesses when it reads from or writes to
register address 400001.
The master defines the type of the data (input or
output). The value is transmitted in a Modbus frame
consisting of two 16- bit words. If the value is 16-bit, it
is transmitted in the LSW (least significant word). If
the value is 32-bit, the subsequent parameter is also
reserved for it and must be set to None.
None.
Control Word (16 bits).
Reference REF1 (16 bits).
Reference REF2 (16 bits).
Status Word (16 bits).
Actual value ACT1 (16 bits).
Actual value ACT2 (16 bits).
Control Word (32 bits).
Reference REF1 (32 bits).
Reference REF2 (32 bits).
Status Word (32 bits).
Actual value ACT1 (32 bits).
Actual value ACT2 (32 bits).
Control Word 2 (16 bits).
When a 32-bit control word is used, this setting means
the most-significant 16 bits.
Status Word 2 (16 bits).
When a 32-bit control word is used, this setting means
the most-significant 16 bits.
Parameter
10.99 RO/DIO control
Parameter
13.91 AO1 data
Parameter
13.92 AO2 data
Parameter
40.91 Feedback data
Parameter
40.92 Setpoint data
See
Terms and abbreviations (page
word.
storage.
storage.
storage.
storage.
169).
Parameters 487
Def / Type
FbEq 16b / 32b
1 = 1
CW 16bit / uint32
0
1
2
3
4
5
6
11
12
13
14
15
16
21
24
31
32
33
40
41